风机盘管(四管制)性能参数表
参数/型号
|
FP-34
|
FP-51
|
FP-68
|
FP-85
|
FP-102
|
FP-136
|
FP-170
|
FP-204
|
FP-238
|
|
额定风量m³/h
|
高档
|
350
|
540
|
700
|
850
|
1020
|
1360
|
1740
|
2050
|
2400
|
中档
|
250
|
340
|
480
|
580
|
690
|
1000
|
1250
|
1560
|
2100
|
|
低档
|
160
|
240
|
320
|
390
|
460
|
650
|
800
|
1080
|
1620
|
|
三排管额定冷量W
|
高档
|
2080
|
3250
|
4180
|
4610
|
5520
|
7650
|
9300
|
10800
|
12850
|
中档
|
1780
|
2880
|
3450
|
4230
|
4490
|
6850
|
8120
|
9200
|
11050
|
|
低档
|
1660
|
2450
|
2870
|
3760
|
3930
|
6110
|
7350
|
8400
|
8650
|
|
单排管额定热量W
|
1451
|
176
|
2901
|
3626
|
4351
|
5775
|
6887
|
7933
|
8898
|
|
输入功率W
|
WA(M)LA
|
35
|
45
|
55
|
75
|
78
|
110
|
132
|
170
|
200
|
WAG30
|
42
|
55
|
65
|
82
|
102
|
146
|
168
|
190
|
250
|
|
WAG50
|
47
|
62
|
75
|
95
|
110
|
165
|
190
|
230
|
280
|
|
KM2
|
37
|
52
|
62
|
76
|
96
|
134
|
152
|
189
|
228
|
|
噪声值dB
|
WA(M)LA
|
36
|
39
|
40
|
41
|
42
|
44
|
46
|
47
|
50
|
WAG30
|
39
|
42
|
43
|
44
|
45
|
47
|
48
|
50
|
53
|
|
WAG50
|
41
|
44
|
45
|
46
|
47
|
49
|
50
|
52
|
54
|
|
KM2
|
37
|
39
|
40
|
41
|
43
|
44
|
45
|
47
|
50
|
|
三排冷水盘管
|
水量kg/h
|
357
|
522
|
692
|
825
|
985
|
1366
|
1660
|
1929
|
2295
|
水阻kPa
|
3.1
|
8.2
|
13.4
|
25.6
|
28.4
|
14.4
|
21.8
|
32.5
|
49.5
|
|
一排冷水盘管
|
水量kg/h
|
127
|
190
|
252
|
315
|
377
|
503
|
628
|
52
|
878
|
水阻kPa
|
5.2
|
10.7
|
16.8
|
29.9
|
36.1
|
19.5
|
26.7
|
35
|
45
|
|
机组重量kg
|
WA WAG
|
16
|
18
|
21
|
24
|
27
|
36
|
41
|
47
|
52
|
LA
|
24
|
26
|
30
|
32
|
37
|
45
|
48
|
52
|
56
|
|
WM
|
26
|
31
|
33
|
41
|
46
|
59
|
62
|
66
|
68
|
|
KM2
|
19
|
23
|
28
|
29
|
33
|
41
|
44
|
46
|
51
|
注:1.表中冷量、热量测定条件(JB/ T4283-91)为:
2.供冷:DB27℃/WB19.5℃,TW1=7℃,TW2=12℃
3.供热:DB21℃,TW1=60℃
4.高静压机组额定风量是机外30/50Pa时的测定值,其余机组额定风量,不带风口和过滤器是机外余压12Pa时的测定值,带风口和过滤器是机外余压为零时的测定值;
5.如使用工况与标准工况不同,请用样本后附修正系数进行修正,方法为;实际制冷(热)量=额定制冷(热)量*工况修正系数;
6.表中的噪声值是在消声室内,离机组各表面1米处(GB9068)测定的声压级噪声值。